Type and Specification | ||||
---|---|---|---|---|
Dimension | 40*40*52 | |||
Installation type | Unshielded | |||
All the output methods | DC type | NPN | NO | ATL-N20MN1 |
NC | ATL-N20MN2 | |||
NO+NC | ATL-N20MN3 | |||
PNP | NO | ATL-N20MP1 | ||
NC | ATL-N20MP2 | |||
NO+NC | ATL-N20MP3 | |||
Two-wire | NO | ATL-N20MD1 | ||
NC | ATL-N20MD2 | |||
AC type | Two-wire | NO | ATL-N20MA1 | |
NC | ATL-N20MA2 | |||
Detection range | 20mm±10% | |||
Setting distance | 0-22mm | |||
Delay distance | ≤10% detection range | |||
Detection object | Magnetic metal (the detection distance decreases when it is non-magnetic metal) |
|||
Standard detection object | SPCC iron 45*45*1mm | |||
Response frequency | DC: 0.5kHz, AC: 50Hz | |||
Supply voltage | DC type: DC 12-24V (6-36V), impulse (p-p) 10% below; AC type: AC 110-220V (90-250V) 50/60Hz |
|||
Withstand voltage | AC1000V 50/60Hz 1min between charging part and housing | |||
Voltage influence | Inside ±15% rated supply voltage range, at rated supply voltage value, inside ±10% detection distance |
|||
Consumption current | N/P type: ≤13mA, D type: ≤0.8mA, A type: ≤1.7mA | |||
Control output | N/P type: ≤200mA, D type: ≤200mA, A type: ≤200mA | |||
Loop protection | N/P/D type: reversal connection protection, surge absorption, load short-circuit protection, A type: surge absorption |
|||
Ambient temperature & humidity | Operation temperature/storage temperature: -30~65℃ (no freeze, no dew); Operation humidity/storage humidity: 35~95%RH |
|||
Temperature influence | Temperature range -30~65℃, at +23℃, ±15% detection distance; Temperature range -25~60℃, at +23℃, ±10% detection distance |
|||
Insulation impedance | ≥50MΩ (DC500 megameter) between charging part and housing | |||
Material | Housing: Nickel plated brass, Detection surface: ABS | |||
Protection class | IP67 | |||
Cable length | 2m |
ATL-N20MN1/N2
ATL-N20MN3
ATL-N20MP1/P2
ATL-N20MP3
ATL-N20MD1/D2
ATL-N20MA1/A2