Type and Specification | ||||
---|---|---|---|---|
Dimension | M18*1 | |||
Installation type | Unshielded | |||
All the output methods | DC type | NPN | NO | GLJ18A3-8-Z/N1 |
NC | GLJ18A3-8-Z/N2 | |||
NO+NC | GLJ18A3-8-Z/N3 | |||
PNP | NO | GLJ18A3-8-Z/P1 | ||
NC | GLJ18A3-8-Z/P2 | |||
NO+NC | GLJ18A3-8-Z/P3 | |||
Two-wire | NO | GLJ18A3-8-Z/D1 | ||
NC | GLJ18A3-8-Z/D2 | |||
AC type | Two-wire | NO | GLJ18A3-8-J/A1 | |
NC | GLJ18A3-8-J/A2 | |||
Three-wire | NO+NC | GLJ18A3-8-J/A3 | ||
Detection range | 8mm±10% | |||
Setting distance | 0-7mm | |||
Delay distance | ≤10% detection range | |||
Detection object | Magnetic metal (the detection distance decreases when it is non-magnetic metal) |
|||
Standard detection object | SPCC iron 18*18*1mm | |||
Response frequency | DC: 0.8kHz, AC: 50Hz | |||
Supply voltage | DC type: DC 12-24V (6-36V), impulse (p-p) 10% below; AC type: AC 110-220V (90-250V) 50/60Hz |
|||
Withstand voltage | AC1000V 50/60Hz 1min between charging part and housing | |||
Voltage influence | Inside ±15% rated supply voltage range, at rated supply voltage value, inside ±10% detection distance |
|||
Consumption current | N/P type: ≤13mA, D type: ≤0.8mA, A type: ≤1.7mA | |||
Control output | N/P type: ≤200mA, D type: ≤200mA, A type: ≤200mA | |||
Loop protection | N/P/D type: reversal connection protection, surge absorption, load short-circuit protection, A type: surge absorption |
|||
Ambient temperature & humidity | Operation temperature/storage temperature: -30~65℃ (no freeze, no dew); Operation humidity/storage humidity: 35~95%RH |
|||
Temperature range | -25~120℃ | |||
Insulation impedance | ≥50MΩ (DC500 megameter) between charging part and housing | |||
Material | Housing: Nickel plated brass, Detection surface: ABS | |||
Protection class | IP67 | |||
Cable length | 2m |
GLJ18A3-8-Z/N1/N2
GLJ18A3-8-Z/N3
GLJ18A3-8-Z/P1/P2
GLJ18A3-8-Z/P3
GLJ18A3-8-J/A1/A2
GLJ18A3-8-J/A3
GLJ18A3-8-Z/D1/D2